Use to optically isolate one piece or local group of RS485 equipment from the rest of an RS485 system, or as a repeater to expand an existing RS485 system beyond the standard's 32-node limitation. The Black Box ICD102A can be used to connect equipment meant for a point-to-point RS422 4-wire interface to an RS485 2-wire multidrop system in factory automation, building automation, and process automation. It can be mounted using DIN Rail and can withstand operating temperatures of -40 to 176 degrees F (-40 to 80 C).
Key Features
| Technology | |
| Category | Serial Connectivity |
| Serial Interface | |
| Class | Serial Extender |
| Baud Rate | 2400 bps to 115.2 kbps, switch-selectable; other rates available up to 460.8 kbps |
| Flow Control | RS-485: 2-wire half-duplex or 4-wire full-duplex; RS-422: Full-duplex |
| Serial Isolation | 2000 VRMS for 1 minute of optical isolation of data lines |
| Power | |
| Surge Protection | Bidirectional overvoltage suppressor: 6.5 V; Peak power dissipation: 600 W; Capacitance (maximum): 3000 pF |
| Ratings | |
| Operating Temperature | -40 to 176° F (-40 to 80° C) |
| Humidity | Up to 95%, non-condensing |
| Download Name | File Size |
| Black Box Converter, Repeaters, Fiber Driver Datasheet | 435.9KB |